Physical Features |
|
| Dimension (W×H×D) | 90mm × 80mm × 62mm |
| Power dissipation | 7W |
|
Memory |
|
| Program memory | 6KB, 4K for common users, 2K for encrypted users |
| Data memory | 2KB |
| Power-failure retention power | button battery |
|
General |
|
|
Timers in total 1ms 10ms 100ms |
128(T0-T127) 4 16 108 |
| Counters in Total | 128 (button battery) |
| Internal memory bit | 128 (button battery) |
| Power-failure retention of internal memory | 112 |
| Time interrupts | 2×1ms resolution |
| Edge interrupts | 4 rising edges / falling edges |
| Boolean execution speed | 0.5µs |
| Float execution speed | 16µs |
| Runtime clock | Available |
|
Integrated Communication Function |
|
| Communication port | PORT0: RS485 |
| PPI Baud Rate | 9.6, 19.2kbps |
|
Maximum cable length per segment Isolated repeater applied Isolated repeater unapplied |
38.4k for 1200m 50m |
| Maximum number of stations | 4 stations per segment, 32 stations per network |
| Maximum number of masters | 16 |
| Point to point (PPI Mater Mode) | N/A |
|
Power Function |
|
| Input Voltage | 85-264V AC (47-63Hz) |
| +5V power for the extended bus | N/A |
| 24 VDC Sensor Power supply | 240 mA |
|
I/O |
|
| Number of integrated Digital inputs | 8 |
| Input type | Sink / Source |
| Number of integrated Digital outputs | 6 |
| Output type | Relay, dry contact |
| Digital I/O mapping area | 128 (64 inputs / 64 outputs) |
| Analog I/O mapping area | 32 (16 inputs / 16 outputs) |
| Maximum number of expandable I/O modules | 0 |
| Maximum number of digital I/O | 14 |
| Maximum number of analog I/O | 0 |
| Pulse Catch inputs | 8 |
|
High-speed counters Single phase counters |
4×50KHz. Support HSC0, HSC3, HSC4 and HSC5. Do not support HSC1 and HSC2 |
|
Digital Input Features |
|
| Number of integrated digital input | 8 |
| Input type | Sink / Source |
| Rated voltage | 24V DC |
| Maximum continuous permissible voltage | 30V DC |
|
Logical 1 Signal (minimum) Logical 0 Signal (Maximum ) |
14V DC, 2.5mA 5V DC, 1mA |
|
Isolation (field side and logical circuit) Optical isolation (Galvanic) Isolation group |
500V AC, 1 minute Refer to the Terminal Identification |
| Simultaneous Inputs | 8 |
|
Maximum cable length Shielded Unshielded |
500m (standard input), 50m (high-speed counter input) 300m (standard input) |
|
Digital Output Features |
|
| Number of integrated digital output | 6 |
| Output type | Relay, dry contact |
|
Maximum rated current of each output Surge Current |
2A 5A, 4S@10% duty ratio |
| Lamp load(Max) | 30W DC / 200W AC |
| On- state resistance | 0.2 ohm |
| Simultaneous output | 6 |
| Two parallel outputs | N/A |
|
Maximum cable length Shielded Unshielded |
500m (standard output) 150m (standard output) |