Physical Features
Dimension (W×H×D) 137mm × 80mm × 62mm
Power Dissipation  10W
 
Memory Features
Program Memory 12KB, 8KB for common user, 4KB for encrypted users
Data Memory 8KB
Power-failure retention power  button batter
 
General Features
  Timers in total 
      1ms
      10ms
      100ms
128 (T0-T127)
4
16
108
Counters in total  128 (button battery)
Internal Memory Bits 256 (button battery)
Time interrupts 2×1ms resolution
Edge interrupts 4 rising edges / falling edges
Boolean execution speed 0.5µs
Float execution speed 16µs
Runtime clock Available
 
Integrated Communication Features
Communication ports 2 ports.  PORT0:PPI, RS485 PWL; FPROT: free port, RS485
PPI Baud Rate 9.6, 19.2kbps
Baud Rate of Freeport  1.2k to 115.2kbps
Maximum cable length per segment 
      Isolated repeater applied
      Isolated repeater unapplied
38.4k for 1200m.
50m
Maximum number of stations 4 stations per segment, 32 stations per network
Maximum number of masters 16
Point to point (PPI  Mater Mode) N/A
 
Power Function
Input Voltage 85-264V AC (47-63HZ)
+5V power for the extended bus 500mA
24V DC Sensor Power supply 150mA
 
I/O Features
Number of integrated Digital inputs 14
Input type Sink / Source
Number of integrated Digital outputs 10
Output type Relay, dry contact
Digital I/O mapping area 128 (64 inputs/64 outputs)
Analog I/O mapping area 32 (16 inputs/16 outputs)
Maximum number of expandable I/O 
modules
3
Maximum number of digital I/O 120
Maximum number of analog I/O 12AI / 6AO
Pulse catch inputs 14
 
Digital Input Features 
Integrated Digital Input 14
Input type Sink / Source 
Rated Voltage 24V DC
Maximum continuous permissible 
voltage
30V DC
Logical 1 Signal (Minimum)
Logical 0 Signal (Maximum)
14V DC, 2.5mA
5V DC, 1mA
Isolation (field side and logical circuit)
      Optical isolation (Galvanic)
      Isolation group
 
500V AC, 1 minute 
Refer to the Terminal Identification
Simultaneous Inputs 14
Maximum cable length
      Shielded
      Unshielded
 
500 m (standard input) and 50m (high-speed counter input)
300 m (standard input)
 
Digital Output Features
Number of integrated digital output 10
Output type Relay, dry contact
Maximum rated current of each 
output
Surge Current 
2A
5A, 4S@10%
Lamp load (Max) 5W
On-state resistance 0.3 ohm, Max: 0.6 ohm
High-speed pulse output 2×50KHz, Q0.0, Q0.1and Q0.2, directionless output. 
Support MC_PTP_R/MC_SPEED_CTRL etc. of CPU. 
Do not support PTO/PWM of programming software
Simultaneous output 8
Two parallel outputs  only when the two outputs are in the same group
Maximum cable length
      Shielded
      Unshielded
 
500m(standard output)