Physical Features |
|
| Dimension (W×H×D) | 137mm × 80mm × 62mm |
| Power Dissipation | 10W |
|
Memory Features |
|
| Program Memory | 12KB, 8KB for common user, 4KB for encrypted users |
| Data Memory | 8KB |
| Power-failure retention power | button batter |
|
General Features |
|
|
Timers in total 1ms 10ms 100ms |
128 (T0-T127) 4 16 108 |
| Counters in total | 128 (button battery) |
| Internal Memory Bits | 256 (button battery) |
| Time interrupts | 2×1ms resolution |
| Edge interrupts | 4 rising edges / falling edges |
| Boolean execution speed | 0.5µs |
| Float execution speed | 16µs |
| Runtime clock | Available |
|
Integrated Communication Features |
|
| Communication ports | 2 ports. PORT0:PPI, RS485 PWL; FPROT: free port, RS485 |
| PPI Baud Rate | 9.6, 19.2kbps |
| Baud Rate of Freeport | 1.2k to 115.2kbps |
|
Maximum cable length per segment Isolated repeater applied Isolated repeater unapplied |
38.4k for 1200m. 50m |
| Maximum number of stations | 4 stations per segment, 32 stations per network |
| Maximum number of masters | 16 |
| Point to point (PPI Mater Mode) | N/A |
|
Power Function |
|
| Input Voltage | 85-264V AC (47-63HZ) |
| +5V power for the extended bus | 500mA |
| 24V DC Sensor Power supply | 150mA |
|
I/O Features |
|
| Number of integrated Digital inputs | 14 |
| Input type | Sink / Source |
| Number of integrated Digital outputs | 10 |
| Output type | Relay, dry contact |
| Digital I/O mapping area | 128 (64 inputs/64 outputs) |
| Analog I/O mapping area | 32 (16 inputs/16 outputs) |
|
Maximum number of expandable I/O modules |
3 |
| Maximum number of digital I/O | 120 |
| Maximum number of analog I/O | 12AI / 6AO |
| Pulse catch inputs | 14 |
|
Digital Input Features |
|
| Integrated Digital Input | 14 |
| Input type | Sink / Source |
| Rated Voltage | 24V DC |
|
Maximum continuous permissible voltage |
30V DC |
|
Logical 1 Signal (Minimum) Logical 0 Signal (Maximum) |
14V DC, 2.5mA 5V DC, 1mA |
|
Isolation (field side and logical circuit) Optical isolation (Galvanic) Isolation group |
500V AC, 1 minute Refer to the Terminal Identification |
| Simultaneous Inputs | 14 |
|
Maximum cable length Shielded Unshielded |
500 m (standard input) and 50m (high-speed counter input) 300 m (standard input) |
|
Digital Output Features |
|
| Number of integrated digital output | 10 |
| Output type | Relay, dry contact |
|
Maximum rated current of each output Surge Current |
2A 5A, 4S@10% |
| Lamp load (Max) | 5W |
| On-state resistance | 0.3 ohm, Max: 0.6 ohm |
| High-speed pulse output |
2×50KHz, Q0.0, Q0.1and Q0.2, directionless output. Support MC_PTP_R/MC_SPEED_CTRL etc. of CPU. Do not support PTO/PWM of programming software |
| Simultaneous output | 8 |
| Two parallel outputs | only when the two outputs are in the same group |
|
Maximum cable length Shielded Unshielded |
500m(standard output) 150m(standard output) |