Physical Features |
|
| Dimension (W×H×D) | 198mm × 80mm × 62mm |
| Power Dissipation | 17W |
|
Memory Features |
|
| Program Memory | 12KB, 8KB for common users, 4KB for encrypted users |
| Data Memory | 8KB |
| Power-failure retention power | button batter |
|
General Features |
|
|
Timers in total 1ms 10ms 100ms |
128 (T0-T127) 4 16 108 |
| Counters in total | 128 (button battery) |
| Internal Memory Bits | 256 (button battery) |
| Time interrupts | 2 × 1ms resolution |
| Edge interrupts | 4 rising edges / falling edges |
| Boolean execution speed | 0.5µs |
| Float execution speed | 16µs |
| Runtime clock | Available |
|
Integrated Communication Features |
|
| Communication ports | 2 ports: PORT0: PPI, RS485 PWL; FPROT: free port, RS485 |
| PPI Baud Rate | 9.6, 19.2kbps |
| Baud Rate of Freeport | 1.2k to 115.2kbps |
|
Maximum cable length per segment Isolated repeater applied Isolated repeater unapplied |
38.4k for 1200 m. 50 m |
| Maximum number of stations | 4 stations per segment, 32 stations per network |
| Maximum number of masters | 16 |
| Point to point (PPI Mater Mode) | N/A |
|
Power Function |
|
| Input Voltage | 85-264V AC (47-63Hz) |
| +5V power for the extended bus | 500mA |
| 24 VDC Sensor Power supply | 240mA |
|
I/O Features |
|
| Number of integrated Digital inputs | 24 |
| Input type | Sink / Source |
| Number of integrated Digital outputs | 16 |
| Output type | Relay, dry contact |
| Digital I/O mapping area | 128 (64 inputs / 64 outputs) |
| Analog I/O mapping area | 32 (16 inputs / 16 outputs) |
|
Maximum number of expandable I/O modules |
3 |
| Maximum number of digital I/O | 128 |
| Maximum number of analog I/O | 12AI / 6AO |
| Pulse catch inputs | 24 |
|
High-speed counters Single phase counters Double phase counters |
3×50KHz: Support HSC0, HSC, HSC2 and HSC3; do not support HSC4 and HSC5. 1×30KHz: support9, HC0 |
|
Digital Input Features |
|
| Integrated Digital Input | 24 |
| Input type | Sink / Source |
| Rated Voltage | 24V DC |
|
Maximum continuous permissible voltage |
30V DC |
|
Logical 1 Signal (minimum) Logical 0 Signal (Maximum ) |
14V DC, 2.5mA 5V DC, 1mA |
|
Isolation( field side and logical circuit) Optical isolation(Galvanic) Isolation group |
Yes 500V AC, 1 minute Refer to the Terminal Identification |
| Simultaneous Inputs | 24 |
|
Maximum cable length Shielded Unshielded |
500 m (standard input) and 50m (high-speed counter input) 300 m (standard input) |
|
Digital Output Features |
|
| Number of integrated digital output | 16 |
| Output type | Relay, dry contact |
|
Maximum rated current of each output Surge Current |
2A 5A, 4S@10% duty ratio |
| Lamp load(Max) | 30 W DC / 200 W AC |
| On- state resistance | 0.2 ohm |
| Simultaneous output | 16 |
| Two parallel outputs | only when the two outputs are in the same group |
|
Maximum cable length Shielded Unshielded |
500m (standard output) 150m (standard output) |