Description PLC100-ED12R, 8DO×RELAY
 
Physical Features
Dimensions (W×H×D) 46mm × 80mm × 62mm
Power loss (dissipation) 2W
 
Output Features
Number of integrated outputs 8
Output type Relay, dry contact
Output Voltage DC: 5~30V, AC: 5~250V
 
Output Current
Logic 1 signal
Number of output groups
Per group mounting (maximum)
Number of output ON (maximum)
Maximum current per group
Lamp load
contact resistance
Surge current
Overload protection
2 A
2
4
8
8 A
5 W
0.2 ohm
8 A for 100 ms, maximum
No
 
Isolation
In group of
Isolation coil to contact
Isolation between open contacts
Isolation resistance
4 points
1500 VAC for 1minute
750 V AC for 1 minute
100M ohm, minimum when new
 
Relay Features
Switch delay
Switch Frequency
Lifetime mechanical (no load)
Lifetime contacts at rated load
15 ms, maximum
1 Hz
5,000,000 open / close cycles
300,000
 
Cable Length
Unshielded 150 m
Shielded 500 m
 
Power Consumption
From +5V(from I/O bus)
From L+
L+ coil power voltage range
56 mA
9 mA per output when ON
20.4 to 28.8 V DC