| Features | 16 DI × 24 V DC, 16 DO × Relay |
|
Physical Features |
|
| Dimension (W×H×D) | 138mm × 80mm × 62mm |
| Power Consumption | 6 W |
|
Input Features |
|
| Number of Inputs | 16 |
| Input Type | Sink/Source |
|
Input Voltage |
|
| Rated Voltage | 24 V DC |
| The Maximum permissible Voltage | 30 V DC |
| Surge Voltage | 35 V DC, 0.5 s |
| Signal "1" | 14 V DC, 2.5 mA |
| Signal "0" | 5 V DC, 1 mA |
|
Isolation |
|
| Optical Isolation | 500 V AC, Duration: within 1 minute |
| Number of Isolation points per group | 8 |
| The longest Input Delay | 4.5 millisecond |
| Sink Current | Max: 1 mA AC |
|
Length of Cable |
|
| Unshielded | 300 m |
| Shielded | 500 m |
|
Simultaneous Inputs |
|
| 40℃ | 16 |
| 50℃ | 16 |
|
Output Features |
|
| Number of Outputs | 16 |
| Type of Output | Relay, Dry contract |
| Output Current | 0.75 A |
|
Signal "1" Number of Output Groups Number of Outputs per group Simultaneous Outputs Maximum Current per group Lamp Load Contact Resistance Peak Current per point Surge Current Max. |
2 A 4 4 16 8 A DC: 30 W, AC: 200 W 0.2 Ω 7 A, Electric shock closed External provide |
|
Isolation |
|
|
Number of Isolation Points Per group Between coil and power supply Between coil and contact point Resistance |
4 × 1500 V AC,duration: within 1 minute Min:100Ω |
|
Relay Features |
|
|
Switch Delay Switch Frequency Mechanical Switch Frequency Contact point lifetime |
15mS 1HZ 10.000.000 100.000 |
|
Length of Cable |
|
| Unshielded | 150 m |
| Shielded | 500 m |
|
Power Waste |
|
| +5V DC Consumption Current | 138 mA |
| L+ | 9 mA when connected |
| L+ Coil Voltage Range | 20.4-28.8 V DC |