| Product Code | PLC300-C34R |
| Description | CPU, Relay |
|
Physical Features |
|
| Size (W×H×D) | 137 mm × 80 mm × 62 mm |
| Power dissipation | 7 W |
| Power supply | AC: 85 V~265 V |
| Rated power supply | 220 V AC |
|
Memory Features |
|
| Program memory | 12KB, expandable to 16KB |
| Data memory | 8KB |
| Super capacitor | About 112 hours (typical) |
| External battery (Optional) | About 200 days (typical) |
|
General Features |
|
|
Timers total 1ms 10ms 100ms |
256 4 16 236 |
| Counters total | 256 (back up by super capacitor) |
| Internal memory bits | 256 (back up by super capacitor) |
| Stored permanently on power down | 112 |
| Time Interrupts | 2 with 1ms resolution |
| Edge Interrupts | 4 rising edges and / or 4 falling edges |
| Analog adjustment | 2 with 8 resolution |
| Boolean execution speed | 0.15µs |
| Float execution speed | 8µs |
| Clock | embedded |
|
Integrated Communication Function |
|
| Communication Interface | 2 communication ports, PORT0: PPI port, RS485; FPORT0: freeport, RS485 PWL |
| PPI baud rates | 9.6, 19.2 and 187.5k |
| Freeport baud rates | 1.2 kbaud to 115.2k |
|
Maximum cable length per segment Isolated repeater applied Isolated repeater unapplied |
When it is 1000 m, baud rate is 187.5k; when it is 1200 m, 38.4k. 50 m |
| Maximum number of stations | 32 stations per segment, 126 stations per network |
| Maximum number of masters | 32 |
| Point to point (PPI Master Mode) | Yes (NWTR / NETW), 8 total, 2 reserved |
|
I/O Features |
|
| Number of integrated digital inputs | 14 |
| Input type | Sink / Source |
| Number of integrated digital outputs | 10 |
| Output type | Relay dry contact |
| Digital I/O mapping domain | 256 (128 inputs / 128 outputs ) |
| Analog I/O mapping domain | 64 (32 inputs / 32 outputs ) |
| Maximum number of expandable I/O modules | 7 |
| Maximum number of digital I/O | 230 |
| Maximum number of analog I/O | 56AI / 28AO |
| Pulse catch inputs | 14 |
|
High-speed counters Total Uniphase counters Bi-phase counters |
2(HSC0 and HSC1) 2×30 KHz 2×20 KHz |
|
Digital Input Features |
|
| Number of integrated digital input | 14 |
| Input type | Sink / Source (IEC Type 1/Source) |
| Rated voltage | 24 V DC |
| Maximum continuous permissible voltage | 30 V DC |
|
Logical 1 Signal (minimum) Logical 0 Signal (Maximum ) |
18 V DC, 2.5 mA 5 V DC, 1 mA |
|
Isolation (field side to logical circuit) Optical isolation(Galvanic) Isolation groups |
Yes 500 V AC, 1 minute refer to the Terminal Identification |
| Simultaneous inputs | 14 |
|
Maximum cable length Shielded Unshielded |
500 M (standard input) 50 M (high-speed counters input) 300 M (standard input) |
|
Digital Output Features |
|
| Output type | Relay dry contact |
| Rated voltage | -- |
|
Maximum rated current of each point Surge current (Max) |
2 A 5 A, contacts closed |
| Lamp load (Max) | 30 W DC / 200 W AC |
| On- state resistance | 0.2 ohm |
|
Delay (Max) off to on on to off |
30ms (Max) |
| High-speed Pulse Output | -- |
| Switching frequency (Max) | 1 Hz |
| Mechanical life cycle | 10 million times (Zero Load) |
| Contact endurance | 0.1 million times (Rated Load) |
| Simultaneous output | 10 |
| Parallel output | Only when the outputs are in the same group |
|
Maximum cable length Shielded Unshielded |
500M (Standard Input) 150M (Standard Input) |