Product Code PLC300-ED32R8 PLC300-ED32R16
Description Digital Output, 8 DO × RELAY Digital Output,16 DO × RELAY
 
Physical Features
  Dimensions (W×H×D) 46 × 80 × 62 mm 71.2 × 80 × 62 mm
  Power loss (dissipation) 2W 3W
 
Output Features
  Number of Integrated Outputs 8 16
  Output Type Relay, dry contact
  Output Voltage DC: 5~30V, AC: 5~250V
 
Output Current
       Logic 1 signal
       Number of output groups
       Per group mounting (maximum)
       Number of output On (maximum)
       Maximum current per group
       Lamp load
       contact resistance
       Surge current
       Overload protection
2 A
2
4
8
8 A
5 W
0.2 ohm
8 A for 100ms, maximum
No
0.5 A
4
4
16
8 A
5 W
0.2 ohm
7 A with contacts closed
No
 
Isolation
      In group of
      Isolation coil to contact
      Isolation between open contacts
      Isolation resistance
4 points
1500 V AC for 1minute
750 V AC for 1 minute
100M ohm, minimum when new
 
Relay Features
      Switch delay
      Switch Frequency
      Lifetime mechanical (no load)
      Lifetime contacts at rated load
15ms, maximum
1Hz
10,000,000 open / close cycles
100,000
 
Cable Length
      Unshielded 150 m
      Shielded 500 m
 
Power Consumption
      From +5V(from I/O bus)
      From L+
      L+ coil power voltage range
40 mA
9 mA per output when On
20.4 to 28.8 V DC