

| Product Code | PLC300-EA31VC |
| Description | Analog Input, 4 AI × 12 bit |
|
Physical Features |
|
| Dimensions (W×H×D) | 71.2 × 80 × 62 mm |
| Power Loss (dissipation) | 2 W |
|
Power Consumption |
|
| From +5 V (from I/O bus) | 34 mA |
| From L+ | 40 mA |
| L+ voltage range, class 2 or DC sensor supply | 20.4~28.8 V DC |
| LED indicator |
24 V DC Power Supply. ON = Normal, OFF = 24 V DC Power Off |
|
Analog Input Features |
|
| Number of analog input points | 4 points |
| Isolation (field side to logic circuit) | Optical isolated: 500 V AC, 1 minute |
| input type | Differential |
| Input Range | |
| Voltage (unipolar) | 0~10 V, 0~5 V |
| Voltage (bipolar) | ±5 V, ±2.5 V |
| Current | 0~20 mA |
| Data Range | 15~30 V |
| Bipolar, full-scale range | 0~32000 |
| Unipolar, full-scale range | -32000~32000 |
|
Input Resolution |
|
| Voltage (unipolar) |
2.5 mV (0~10 V) 1.25 mV (0~5 V) |
| Voltage (bipolar) |
2.5 mV (±5 V) 1.25 mV (±2.5 V) |
| Current | 5 μA (0~20 mA) |
| Analog to digital conversion time | <300 μs |
| Analog input step response | 1.5 ms |
| Common mode rejection | 40 Db, DC to 60 Hz |
| Common mode voltage | Signal voltage + Common mode voltage < 12 V |
| Input Impedance | ≥10 MΩ |
| Input filter attenuation | -3 db @ 3.1 KHz |
| Maximum input voltage | 30 V |
| Maximum input current | 30 mA |
| ADC resolution | 12 bit |