| Product Code | PLC500-C56M2 | PLC500-C56M4 |
| Memory | 2 MB | 4 MB |
|
Physical Features |
||
| Dimension | 34 mm × 115 mm × 102 mm | |
| Rated Power | 19.2 W | |
| Rated Input Voltage | 24 V | |
| Input Current | 0.8 A (Reverse polarity protected) | |
| Bus Power Voltage | 5 V DC | |
| Bus Power Current | 1.6 A | |
|
LED Indicators |
||
| 24 V Power LED | Green On: power normal, Off: power off | |
| SF LED | Red On: system down, Off: system normal | |
| BF LED | Red On: bus down, Off: bus normal | |
| Run LED | Green On: system running, Off: system stops | |
| Stop LED | Orange On: system stops, Off: system running | |
| Ethernet LED | Green Flash: connected, Off: disconnected; Yellow On: 100 Mbps, Off: 10 Mbps | |
|
Command Performance |
||
| Bit Instruction Execution Speed | 0.01 µs / step | |
| Floating Point Instruction Execution Speed | 1 µs / step | |
|
Ethernet Communication Port |
||
| Communication Port | 1 standard | |
| Protocol Type | UDP protocol | |
| Baud Rate | 10 / 100 Mbps, adaptable | |
| Cable Length per Segment, Max. | 100 m | |
| Stations, Max. | 32 connections, supported by Modbus TCP | |
| Isolation | Available | |
|
EtherCAT Communication Port |
||
| Communication Ports | 2 | |
| Protocol Type | EtherCAT | |
| Cable Length per Segment, Max. | 100 m | |
| Stations, Max. | 128 servo slave stations | |
| Support | Redundancy setting, distributed clock setting, boot parameters configuration, PDO parameters configuration and mapping, bus cycle configuration, | |
| Isolation | Available | |
|
RS485 Communication Port |
||
| Communication Port No. | 1, Port0 | |
| Protocol Type | PPI, Freeport of Modbus | |
| Communication Baud Rate | 1.2 Kbps to 115.2 Kbps, built-in Modbus master / slave function | |
| Cable Length per Segment, Max. | Isolation relay in use: 1000 m for 187 Mbps and 1200 m for 38.4 Mbps, Isolation relay Not in use: 50 m | |
| Stations, Max. | 32 stations per segment, 126 stations per network | |
| PPI Master Mode | Read / write 200 bytes each, 8 literacy instructions allowed simultaneously | |
| Isolation | Communication port isolation | |
|
Program Software |
||
| Programming Package | Codesys V3 | |
| Programming Language | CFC / FBD / LD / IL / ST / SFC | |
|
Protection |
||
| Power Protection | Reverse polarity and surge protection | |
| Interface Protection | Lightning protection at communication port | |
| Power-Off Protection Space | 32 KB | |
|
Extension I/O |
||
| Max. Frames | 4 | |
| Max. Modules | 11 | |
|
Real Time Clock |
||
| Back-Up | Typically 112 hours | |
| Accuracy | Deviation of less than 60 seconds per month | |