Product Code PLC500-EC51
 
Physical Features
Dimension(W×H×D) 34 × 115 × 101.6 mm
 
Power
Rated input voltage 24 V DC
Input voltage range 20.4 V~28.8 V DC
Input current 100 mA
Reverse polarity protection Yes
Bus power voltage +5 V DC
Bus power current 100 mA
 
LED Lights Diagnostics
24 V LED On:24 V DC  Power Normal, Off: 24 V DC Power Unavailable
SF LED On: System-down, Off: Normal, flash: Input signal error
BF On: Slave configuration not completed, Off: All slave configuration completed.
DX On: slave diagnostic, Off: no diagnostic
 
CANopen Communications
Communication Interface 1 CAN communication Interface
The maximum number of master Support 8 masters at most for one CPU
The maximum number of slave  Support 32 slaves at most for one master 
Cable Length with Transmission Rate 25 m (1000 Kbit/s), 100 m (500 Kbit/s), 250 m (250 Kbit/s), 1000 m (50 Kbit/s)
Isolation Communication port isolation