Product Code PLC500-ET51A4 PLC500-ET51A8
 
Physical Characteristics
Dimension (W×H×D) 34 × 115 × 100 mm
 
Power
Rated input voltage 24 V DC
Input voltage range 20.4 V~28.8 V DC
Input current 50 mA
Reverse polarity protection Yes
Bus power voltage +5 V DC
Bus power current 50 mA
 
LED Indicator
24V power LED On: 24 V DC normal power, Off: 24 V DC Power Unavailable
SF LED On: System down, Off: Normal, Flash: Input signal error
 
Input Features
Input type Suspension-type thermocouple
Number of inputs 4 8
Wiring -
Input Range Thermocouple type (choose one): S, T, R, E, N, K, J. Voltage range: ± 80 mV.  Default: K
 
Isolation 
Field to Logic 
Site to 24 V DC 
24 V DC to logic
500 V AC
500 V AC
500 V AC
Common Mode Rejection >100 dB @ 120 V AC
 
Input resolution
Temperature 
Voltage 
Resistance
0.1℃ / 0.1℉
-
15 + sign bit
Measuring principle Sigma-Delta
Module update frequency (all channels) 4 channel support 8Hz,  4Hz, 2Hz, 1Hz configured, default : 2Hz all channels
8 channel support 4Hz, 2Hz, 1Hz, 0.5Hz configured, default : 2Hz all channels
length of wire to sensor Max. 100m
Wire loop resistance 100 Ω
Noise suppression 85 dB @ 50 Hz / 60 Hz / 400 Hz
Data word format Voltage: -27648 ~ +27648
Input impedance >10 MΩ
Maximum input voltage Inputs can support a maximum voltage to 30 V DC of misconnection
Resolution 15bit + sign bit
Input filter attenuation -3 dB @ 21 KHz
Basic error 0.1% Fs (voltage)
Repeatability 0.05% Fs
Cold junction compensation Can be configured, default: yes
Cold junction error ±1.5℃
Temperature Unit Celsius / Fahrenheit can be configured,  default Celsius
Break detection Configuration available, Support both positive and negative directions calibration, default positive calibration
 
Diagnostic 
Break  32767 (positive calibration), -32768 (negative calibration)
No module supply 32766
With integrated PID control function No